Analisis Kualitas Daya dan Rekomendasi Perbaikan Sistem Kelistrikan di Gedung Perhotelan

Authors

  • Ahmad Hermawan Politeknik Negeri Malang
  • Jamik Apriliasari Politeknik Negeri Malang
  • Chandra Wiharya Politeknik Negeri Malang

DOI:

https://doi.org/10.33795/elposys.v10i2.1220

Keywords:

Power Quality, Overvoltage, Undervoltage, Voltage Unbalance, Current Unbalance, Power Factor, Harmonics, ETAP.

Abstract

Fave Hotel is supplied by 2 PLN transformers, with capacities of 250 kVA and 100 kVA. The supply of electrical energy at Fave Hotel is very important because the possibility of disruption is very large in the process of distributing electrical energy. Load variations at Fave Hotel will also affect the electrical system. One of the disturbances that occur in the electric power system is power quality. The research method used is data observation, monitoring, analysis, and simulation using ETAP software. Based on the results of the analysis of various power quality parameters that were measured, the power quality conditions of the fave hotel were not good. A power quality problem has been identified at Fave Hotel, specifically a voltage imbalance occurs at MDP 2 on weekend is 2.64%. In addition, there is also a current imbalance occurs at MDP 1 and 2 during both weekends and weekdays, with the largest current imbalance occurs at MDP 2 on weekdays is 64.15%. To overcome the problem of voltage imbalance and current imbalance, it is recommended to perform load balancing on the system or install compensating equipment such as a voltage compensator.

References

M. S. Rad, M. KazeroonI, M. J. Ghorbany, & H. Mokhtari, “Analysis of The Grid Harmonics and Their Impact on Distribution Transformers,” IEEE Power Energy Conferens, 2012.

SPLN, “SPLN 70-1. Jakarta: PT. Perusahaan Listrik Negara (Persero), 1995.

SPLN, SPLN 1:1995. Jakarta: PT. Perusahaan Listrik Negara (Persero), 1995.

Dugan, R. C., McGranaghan, M. F., Santoso, S., & Beaty, H. W. (2004). Electrical Power Systems Quality, Second Edition (Second).

IEEE std 1159, “IEEE Recommended Practice for Monitoring Electric Power Quality.” 2009.

Hakim, M. F., Herman, B. Y. V., & Himawan, H. M. (2021). AUDIT PENERANGAN PADA GEDUNG A, B, DAN C DI PERGURUAN TINGGI. Elposys: Jurnal Sistem Kelistrikan, 8(2), 36–40.

Dasa Novfowan. A, Mieftah. M, & Kusuma. W, “Alternatif Penanganan Losses Akibat Ketidakseimbangan Beban Pada Trafo Distribusi,” ELPOSYS: Jurnal Sistem Kelistrikan, vol. 10, no. 1, p. 54.

M. D. T. Sogen, “Analisis Pengaruh Ketidakseimbangan Beban Terhadap Arus Netral dan Losses pada Transformator Distribusi di PT PLN (Persero) Area Sorong,” Jurnal Electro Luceat, vol. 4, 2018.

Suheta, T., & Haryudo, S. I. (n.d.). Pengaruh Harmonisa Pada Gardu Trafo Tiang Daya 200 KVA di PT PLN (Persero) APJ Surabaya Utara. Jurnal Teknik Elektro, 7–11

Sugiarto, H. (2012). Kajian Harmonisa Arus Dan Tegangan Listrik di Gedung Administrasi Politeknik Negeri Pontianak. 8.

Sutjipto. R, Kusuma. W, & Zulfianta. K, “Analisis Pengaruh Harmonisa Terhadap Losses Transformator 500kVA,” ELPOSYS: Jurnal Sistem Kelistrikan POLINEMA, vol. 9, no. 2, p. 40.

Downloads

Published

2023-06-14

How to Cite

Ahmad Hermawan, Jamik Apriliasari, & Chandra Wiharya. (2023). Analisis Kualitas Daya dan Rekomendasi Perbaikan Sistem Kelistrikan di Gedung Perhotelan. Elposys: Jurnal Sistem Kelistrikan, 10(2), 101–106. https://doi.org/10.33795/elposys.v10i2.1220