Analisis Pengaruh Skala Warna dan UV-Vis Terhadap Tingkat Penuaan Isolasi Minyak

Authors

  • Galuh Prawestri Citra Handani Politeknik Negeri Malang
  • Rohmanita Duanaputri Politeknik Negeri Malang
  • Rahman Azis Prasojo Politeknik Negeri Malang
  • Sigit Setya wiwaha Politeknik Negeri Malang
  • Divac Nabiel Akbar Politeknik Negeri Malang
  • Galih Pratiti Citra Hastari Politeknik Negeri Malang

DOI:

https://doi.org/10.33795/elposys.v10i3.4445

Keywords:

color scale; themal ageing; transformer; transformer oil insulation; UV-Visible Spectrophotometric

Abstract

A transformer is a static device that can transfer electrical energy using the principle of electromagnetic induction. In operating conditions, the increase of temperature in the transformer will cause the oil insulation having disturbance, which will cause the quality of the insulation to decrease. In this research, oil isolation type shell diala b was chosen which was placed in an accelerated thermal aging chamber experiment device. Then shell diala b oil insulation is heated to a temperature of 120 °C and 160 °C with three sampling times. After this, the oil insulation characteristics were tested which includes oil color scale testing and UV-Visible spectrophotometric testing of the oil. The research method used refers to the IEC 60216-3 2006 standard for aging time and ASTM D-1500 COLOR SCALE for color scale testing. After testing the characteristics of shell diala b oil insulation, it was found that the value of the color scale had increased. Besides that, there has been an increase in the absorption of UV-Visible rays within the oil insulation, which causes the color of the insulation become darker as the temperature and the aging duration in the accelerated thermal aging chamber increases.

References

Katadata, “Proyeksi Kebutuhan Listrik Indonesia 2015-2030,” 2016. https://databoks.katadata.co.id/datapublish/2016/08/04/proyeksi-kebutuhan-listrik-indonesia-2015-2030 (accessed Oct. 28, 2022).

S. Sharma, “Basics of Electrical Engineering,” Basics Electr. Eng., p. 598, 2007.

A. K. Rashed, D. E. A. Mansour, A. Rezk, and M. Ghali, “Effect of Oxidation of Aged Power Transformer Insulating Oil on UV-Vis Spectra,” Proc. - IEEE Int. Conf. Dielectr. Liq., vol. 2022-May, no. 25982, pp. 2–5, 2022, doi: 10.1109/ICDL49583.2022.9830922.

B.L.Theraja and A.K.Theraja, “A Textbook of Electrical Technology AC & DC Machine.” p. 709, 2005.

V. Vasovic et al., “Aging of transformer insulation - Experimental transformers and laboratory models with different moisture contents: Part i - DP and furans aging profiles,” IEEE Trans. Dielectr. Electr. Insul., vol. 26, no. 6, pp. 1840–1846, 2019, doi: 10.1109/TDEI.2019.008183.

T. Mariprasath and V. Kirubakaran, “A critical review on the characteristics of alternating liquid dielectrics and feasibility study on pongamia pinnata oil as liquid dielectrics,” Renew. Sustain. Energy Rev., vol. 65, pp. 784–799, 2016, doi: 10.1016/j.rser.2016.07.036.

R. J. Liao, B. Xiang, L. J. Yang, C. Tang, and H. G. Sun, “Study on the thermal aging characteristics and bond breaking process of oil-paper insulation in power transformer,” Conf. Rec. IEEE Int. Symp. Electr. Insul., pp. 291–296, 2008, doi: 10.1109/ELINSL.2008.4570332.

M. Ahmad, I. Daris, H. Rahmat, and S. Suwarno, “Aging Behavior of Mineral Oil, Gas-to-Liquid (GTL), and Natural Ester Liquids in Presence of Cellulosic Materials,” 2021 3rd Int. Conf. High Volt. Eng. Power Syst. ICHVEPS 2021, pp. 501–506, 2021, doi: 10.1109/ICHVEPS53178.2021.9601042.

C. Widyastuti and R. A. Wisnuaji, “Analisis Tegangan Tembus Minyak Transformator Di PT. PLN (Persero) Bogor,” Elektron J. Ilm., vol. 11, no. 2, pp. 75–78, 2019, doi: 10.30630/eji.11.2.128.

A. Munajad, C. Subroto, and Suwarno, “Fourier transform infrared (FTIR) spectroscopy analysis of transformer paper in mineral oil-paper composite insulation under accelerated thermal aging,” Energies, vol. 11, no. 2, 2018, doi: 10.3390/en11020364.

Suwarno and R. A. Pasaribu, “Thermal aging of mineral oil-paper composite insulation for high voltage transformer,” Int. J. Electr. Eng. Informatics, vol. 8, no. 4, pp. 819–834, 2016, doi: 10.15676/ijeei.2016.8.4.9.

T. Mariprasath and V. Kirubakaran, “A real time study on condition monitoring of distribution transformer using thermal imager,” Infrared Phys. Technol., vol. 90, pp. 78–86, 2018, doi: 10.1016/j.infrared.2018.02.009.

Z. Poniran and Z. A. Malek, “Life assessment of power transformers via paper ageing analysis,” POWERENG 2007 - Int. Conf. Power Eng. - Energy Electr. Drives Proc., pp. 460–465, 2007, doi: 10.1109/POWERENG.2007.4380104.

IEEE C57.91TM, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators - Redline, vol. 2011, no. March. 2012.

IEEE C57.100, IEEE Standard Test Procedure for Thermal Evaluation of Liquid-Immersed Distribution and Power Transformers, vol. 2011, no. December. 2011.

Shell, “Shell Diala S4 ZX-I Sicherheitsdate,” pp. 5–7, 2014.

ASTM International United States, “Standard Test Method for ASTM Color of Petroleum Products ( ASTM Color Scale ) 1,” Annu. B. ASTM Stand., vol. 05, no. October 1959, pp. 1–5, 2011, doi: 10.1520/D1500-12R17.This.

PT. PLN Transmisi Jawa Bagian Timur dan Bali, “Pengujian Warna Disusun : Tim Laboratorium PT PLN (Persero) Transmisi Jawa Bagian Timur dan Bali,” 2018.

A. M. Alshehawy, D. E. A. Mansour, A. Rezk, and M. Ghali, “Impact of thermal aging of transformer oil on UV-Vis optical spectrum and dielectric properties,” 2016 18th Int. Middle-East Power Syst. Conf. MEPCON 2016 - Proc., pp. 860–865, 2017, doi: 10.1109/MEPCON.2016.7836996.

T. K. Saha, “Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers,” IEEE Trans. Dielectr. Electr. Insul., vol. 10, no. 5, pp. 903–917, 2003, doi: 10.1109/TDEI.2003.1237337.

M. Benounis, T. Aka-Ngnui, N. Jaffrezic, and J. P. Dutasta, “NIR and optical fiber sensor for gases detection produced by transformation oil degradation,” Sensors Actuators, A Phys., vol. 141, no. 1, pp. 76–83, 2008, doi: 10.1016/j.sna.2007.07.036.

J. Li, W. Si, X. Yao, and Y. Li, “Partial discharge characteristics over differently aged oil/pressboard interfaces,” IEEE Trans. Dielectr. Electr. Insul., vol. 16, no. 6, pp. 1640–1647, 2009, doi: 10.1109/TDEI.2009.5361584.

S. Karmakar, N. K. Roy, and P. Kumbhakar, “Effect of ageing in transformer oil using UV-visible spectrophotometeric technique,” J. Opt., vol. 40, no. 2, pp. 33–38, 2011, doi: 10.1007/s12596-011-0030-4.

A. Abu-Siada, L. S. Pin, and S. Islam, “Remnant life estimation of power transformer using oil UV-Vis spectral response,” 2009 IEEE/PES Power Syst. Conf. Expo. PSCE 2009, 2009, doi: 10.1109/PSCE.2009.4840111.

IEC 60422, Mineral insulating oils in electrical equipment – Supervision and maintenance guidance. 2013.

Sofyan, Ruslan, and A. Efendi, “Studi Penuaan Minyak Transformator Distribusi,” Pros. Semin. Has. Penelit. 2018, vol. 2018, pp. 63–71, 2018.

PT. PLN, “SPLN 33 - Pedoman Penerapan Metode ASTM untuk Analisa Bahan Bakar Minyak,” Surat Keputusan Direksi PLN, 1980.

Downloads

Published

2023-10-31

How to Cite

Galuh Prawestri Citra Handani, Duanaputri, R., Prasojo, R. A., Wiwaha, S. S., Akbar , D. N., & Hastari , G. P. C. (2023). Analisis Pengaruh Skala Warna dan UV-Vis Terhadap Tingkat Penuaan Isolasi Minyak. Elposys: Jurnal Sistem Kelistrikan, 10(3), 183–188. https://doi.org/10.33795/elposys.v10i3.4445