Analisis Kinerja Sistem Proteksi Berdasarkan Peramalan Beban Pada Penyulang Galunggung
DOI:
https://doi.org/10.33795/elposys.v10i3.4582Abstract
The Galunggung feeder has a total line length of 10.68 kilometers and is supplied by power transformer number 1 at the Polehan substation, with a capacity of 30 MVA. As of December 2020, the peak load on the Galunggung feeder was recorded at 231.4 A, while the lowest load was 133.9 A. Up to the current condition, the Galunggung feeder is operating within standard parameters, with a voltage drop of 0.434 kV or 2.17%. However, it is possible that with future developments and an increase in the number of customers over the years, the energy demand will also increase. Due to this additional energy demand, the protection system may require adjustments to accommodate the increased load.After conducting load forecasting using simple linear regression, a forecast for the next 10 years was obtained. In the year 2030, it is anticipated that the Galunggung feeder will experience a 24% increase in load. With this load increase and no changes to transformers or conductors, there will be no alterations to impedance and short-circuit current calculations. Therefore, no protection setting adjustments are necessary. The recommended action would be to upgrade some transformers that are approaching their capacity limits.
References
(1) M. Mieftah, Sukamdi, Bakti Indra K. 2020. Analisis Aliran Daya Akibat Pengaruh Pengalihan Beban di Kawasan Dieng. Seminar Nasional Teknologi Elektro Terapan. Vol.04, ISSN: 2581-0049.
(2) M. Mieftah, Imron Ridzki, Bakti Indra K. 2021. Analisis Aliran Daya Berdasarkan Peramalan Beban Pada Salah Satu Penyulang Di Malang. Seminar Nasional Teknologi Elektro Terapan. Vol.05, ISSN: 2581-0049.
(3) Hadi Suyono and R. N. Hasanah. 2016. Analysis of power losses due to distribut-ed generation increase on distribution system. Journal Technologi Science and Engineering. 78(6-3), 23-28.
(4) Indra Bakti, Hadi Suyono & Soekotjo Harry. 2017. Injection Analysis of 5 MWp Photovoltaic Power Plant on 20 kV Distribution Network In Kupang. International Journal of Research in Engineering and Science. Vol 5 PP45-50.
(5) Jr. Stevenson D. William. 1983. Elements of Power System Analysis. Four Edi-tion. Terjemahan Idris K. Jakarta: Erlangga.
(6) Kadir Abdul. 2006. Distribusi dan Utilisasi Tenaga Listrik. Jakarta: Universitas Indonesia
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2023 Elposys: Jurnal Sistem Kelistrikan
This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.