Kajian Koordinasi Sistem Proteksi Pada Sistem Transmisi 70 kV GI Banaran Kediri Transmission Line Bay Pare

Authors

  • Hafid Abibie Politeknik Negeri Malang
  • Sulistyowati Politeknik Negeri Malang
  • Ferdian Ronilaya Politeknik Negeri Malang

DOI:

https://doi.org/10.33795/elposys.v7i3.668

Keywords:

substation, transmission, distance relay, OCR, directional earth fault, coordination

Abstract

The substation is one of the components in the electric power distribution system which plays a very important role because it
is the connection between electricity services to customers. In the electric power distribution system, there are disturbances that often occur,
one of which is a short circuit. For that, the way to overcome this is using the Distance Relay protection system, OCR / GFR and DEF. The
purpose of writing this research is to determine the value of setting relay distance, setting Over Current Rele and Directional Earth Fault relay
in order to secure the 70 kV transmission network connected to GI Banaran, which is then simulated using DigSILENT 15.1 software on the
Pare line by calculating symmetrical and asymmetrical disturbances. including 3-phase disturbance on February 1, 2018. The simulation
results show that the 3-phase disturbance occurs at Zone 1 relay distance of the Banaran Bay Pare substation with a trip time of 0.02 seconds
with a fault impedance of 0.083 ohms below the relay impedance value of 0.887 ohms. The coordination between the distance relay on the
side of the Banaran Bay Pare substation has worked well because there is no error reading the relay when it will cut off the disturbance.

References

El-Harawy, Muhamed E.;. (2008). Introduction to Electrical

Power System. USA: John Wiley & Sons.

Gde,Dwi,&Wayan. (2018). Analisis Hubung Singkat Pada

Jaringan Tegangan Menengah 20 kV Penyulang

Kedongaman. Majalah Ilmiah Teknologi Elektro, Vol. 17

Grainger, J., & William, D. J. (2005). Power System Analysis.

D. Stevenson Wiliam.

Halomoan, Cristof Naek;. (2008). Studi Konsep Adaptif.

Indonesia.

Haryanto, Bagus;. (2003). Sistem Pengaman Transmisi.

Indonesia: PT.PLN (Persero) P3B Jawa Bali Region Jawa

Barat.

Horowith, Stanley H.; Phadke, Arun G.;. (2008). Power

System Relaying. USA: John Wiley & Sons.

Parshusip, & Hermawan. (2012). Relay Jarak Sebagai

Pengaman Utama Pada Pola Proteksi SUTT. PT. PLN

(Persero) Udiklat Semarang.

PT. PLN (Persero);. (2014). Proteksi dan Kontrol

Penghantar. Indonesia.

PT.PLN (Persero). (2009). Jasa Pendidikan dan Pelatihan

Proteksi Penyaluran Tenaga Listrik.

PT.PLN (Persero). (2009). Petunjuk Batasan Operasi

SK114 No. 7-22. Indonesia: HARLUR-PST.

Electric Schneider. MiCOM P441/P442/P444 Numerical

Distance Protection.

Syafar, A. Muhammad. (2010). Studi Keandalan Distance

Rele Jaringan 150 kV GI TELLO-GI PARE-PARE. Media

Elektrik, Volume 2.

Yudha, Hendra Marta;. (2008). Proteksi Rele Prinsip dan

Aplikasi. Indonesia: Universitas Sriwijaya Jurusan TE.

Downloads

Published

2020-10-30

How to Cite

Hafid Abibie, Sulistyowati, & Ferdian Ronilaya. (2020). Kajian Koordinasi Sistem Proteksi Pada Sistem Transmisi 70 kV GI Banaran Kediri Transmission Line Bay Pare. Elposys: Jurnal Sistem Kelistrikan, 7(3), 51–57. https://doi.org/10.33795/elposys.v7i3.668